Pump Cable Flat Heavy Duty Jacketed

Description

TYPE – THW, footprint every two feet, 500-0, 1000-0, UL Standard 83

Application

For use within well casing supplying power to the submersible pump. Maximum conductor operating temperatures of –25 C to 75 C in circuits not exceeding 600 volts.

Construction

Conductor: Stranded soft annealed copper

Insulation: Thermoplastic polyvinyl chloride (PVC)

Color Coding: Black, red, yellow, green (ground)

Assembly: Insulated conductors, including the ground conductor, are assembled flat and parallel

Jacket: Black thermoplastic polyvinyl chloride (PVC) extruded over the parallel conductors

Temperature: 75º C

Voltage: 600 Volts

Conductor          
Size (AWG) Stranding Number of Conductors Part Numbers Approx. Ship Wt./M’ Insulation Inner Thickness Jacket Thickness (PVC) Overall Dimensions (in.)
14 19 2 w/grd PCH14/2G 104 0.045 0.045 .191x.513
14 19 3 w/grd PCH14/3G 124 0.045 0.045 .191x.674
12 19 2 w/grd PCH12/2G 131 0.045 0.045 .210x.570
12 19 3 w/grd PCH12/3G 161 0.045 0.045 .210x.750
10 19 2 w/grd PCH10/2G 18 0.045 0.045 .233x.639
10 19 3 w/grd PCH10/3G 246 0.045 0.045 .233x.842
8 19 2 w/#10grd PCH08/2G 260 0.045 0.045 .323x.849
8 19 3 w/#10grd PCH08/3G 342 0.045 0.045 .323x1.113
6 19 3 w/#8grd PCH06/3G 525 0.06 0.045 .359x1.256
4 19 3 w/#8grd PCH04/3G 706 0.06 0.045 .406x1.444
2 19 3 w/#6grd PCH02/3G 1059 0.06 0.045 .466x1.684
1/0 19 3 w/6grd PCH1A/3G 1721 0.08 0.06 .660x1990
2/0 19 3 w/6grd PCH20/3G 2000.3 0.08 0.06 .700x2.120
3/0 19 3 w/4grd PCH30/3G 2506 0.08 0.06 .734x2.314
4/0 19 3 w/4grd PCH40/3G 2999.6 0.08 0.06 .800x2.490

Conductor Color Code

  • 2 conductor = black, red, green ground
  • 3 conductor = black, yellow, red, green ground

Put-Up Codes

  • 1=500’ put-up or 2=1000’ put-up